The Protec 6000/LPZA is zone alarm Interface which allows the 6000 series intelligent addressable loop to interface to a zone of conventional devices and a conventional sounder circuit.

This interface is ideally suited for small conventional fire detection to be fully integrated with Protec Intelligent addressable systems. The 6000/LPZA is loop powered and does not require external power supply. It can support up to 10 Protec conventional (3000PLUS) detectors.

The zone end of line is selectable using the on board DIL switch and can be programmed to resistive or capacitive. The sounder circuit is monitored for open and short circuit faults and has 50mA current
drive capability.

The interface has an inbuilt loop short circuit isolator fitted as standard.